VGP224/ 42.5-140KVA Brushless Synchronous Alternator
    DIY POWER VGP ALTERNATOR

     VGP~224 Series
     
42.5-140 KVA

      Brushless Synchronous Alternator

Rated Date 50Hz - 1500 RPM
Rating kVA/ kW cos Φ=0.8
Duty/Ambient T °  Continuous/ 40℃ Stand by/27℃
Ins. Class/ T  ° Rise H / 125 ° K H/163° K
Phase 3 Phase 3 Phase
Voltage Y 380V 400V 415V 440V 380V 400V 415V 440V
220V 230V 240V
220V 230V 240V
YY

  220V


220V

VGP224S1

KVA 42.542.542.54048484845
kW 3434343238.438.438.436

VGP224S2

KVA 5050504857.557.557.554.75
kW 40404038.446464643.8

VGP224M3

KVA 62.562.562.56072.572.572.570
kW 5050504858585856
VGP224M4 KVA 72.572.572.57083.7583.7583.2581.25
kW 5858585667676765
VGP224L5 KVA 80808076.2592.592.592.588.75
kW 6464646174747471
VGP224L6 KVA 8585857910010010093.75
kW 68686863.280808075
VGP224L7 KVA 93.7593.7593.7586.25111.3

111.3

111.3103.8
kW 7575756989898983

Rated Date60Hz - 1800 RPM
RatingkVA/ kW cos Φ=0.8
Duty/Ambient T ° Continuous/ 40℃Stand by/27℃
Ins. Class/ T  ° RiseH / 125 ° KH/163° K
Phase3 Phase3 Phase
VoltageY380V416V440V480V380V416V440V480V
220V240V 
220V240V220V
YY
208v220V240V


240V

VGP224S1

KVA47.55052.55551.2553.7556.2561.25
kW3840424441434549.2

VGP224S2

KVA57.56062.5656567.57072.5
kW4648505252545658

VGP224M3

KVA6567.572.577.572.5758087.5
kW5254586258606470
VGP224M4KVA8083.7587.593.7586.2593.7598.75105
kW6467707569757984
VGP224M5 KVA 82.588.7593.7510095103.8110118.8
kW 6671758076838895
VGP224L6 KVA 9093.7597.5105102.5110117.5127.5
kW 72757883828894102
VGP224L7 KVA 96.25105111.3117.5113.8123.8130140
kW 778489949199104112
ENVIRONMENT CONDITIONS:
In the following environments, the alternator could run continuously:
1. Altitude: do not exceed 1000m.
2. Cooling air temperature: 250~313K (-15℃~40℃).
3. Relative air humidity: do not exceed 90%.
Note: If environment conditions exceed the scope mentioned-above, please feel free to contact us.
MAIN PERFORMACE DATA:
1.    The standard protection for VGP series generators is IP23;
2.  Winding are insulated to class H;
3.  Full-damping whole salient construction guarantees generator to be operated stably in any conditions, and enable it to run under 150% rated speed(2250 r/min) for 2 minutes;
4.   VGP alternator are provided with a 2/3 winding pitch as standard, can effectively eliminated the third harmonic (3rd, 9th, 15th …etc.), and are therefore perfectly suited to installations with distorting loads, and easy to operate with the other alternator in parallel;
5.  Adjusting rate of stable voltage ≤ 1%, adjusting rate of instant voltage: -15%~+20% (60&ln, COSΦ ≤ 0.4 lagging), instant voltage recovery time ≤ 1.5s;
6.  Wave aberration rate of voltage THD ≤ 3%, telephone harmony wave factor THF ≤ 2%, telephone effective factor of TIF≤ 50. 